In this paper the Feedback Linearization (FL) control theory is applied to a grid-connected Cascaded H-Bridge (CHB) converter. A DC voltage control is designed taking into account the nonlinear model of the converter and its performances are compared with the performances obtained in case of a conventional PI controller. With the aim to provide a fair comparison, the results are evaluated in terms of: settling time in case of a reference voltage variation, voltage overshoot in case of a load variation and total harmonic distortion of the grid current. Simulation and experimental results demonstrate that the FL-based control provides higher power quality and faster response to reference variations than the PI control. Comparing the performances in terms of responses to the load variations, better dynamics performance can be achieved also with the FLbased control increasing the settling time while maintaining an admissible grid current total harmonic distortion index.
CHB Converter DC voltage control based on Feedback Linearization / Sante Pugliese, Rosa A. Mastromauro, Silvio Stasi, Marco Liserre. - ELETTRONICO. - (2018), pp. 4447-4452. (Intervento presentato al convegno 44th Annual Conference of the IEEE Industrial Electronics Society tenutosi a Washington D.C. nel 21-23 Ottobre 2018) [10.1109/IECON.2018.8591549].
CHB Converter DC voltage control based on Feedback Linearization
Rosa A. Mastromauro;
2018
Abstract
In this paper the Feedback Linearization (FL) control theory is applied to a grid-connected Cascaded H-Bridge (CHB) converter. A DC voltage control is designed taking into account the nonlinear model of the converter and its performances are compared with the performances obtained in case of a conventional PI controller. With the aim to provide a fair comparison, the results are evaluated in terms of: settling time in case of a reference voltage variation, voltage overshoot in case of a load variation and total harmonic distortion of the grid current. Simulation and experimental results demonstrate that the FL-based control provides higher power quality and faster response to reference variations than the PI control. Comparing the performances in terms of responses to the load variations, better dynamics performance can be achieved also with the FLbased control increasing the settling time while maintaining an admissible grid current total harmonic distortion index.File | Dimensione | Formato | |
---|---|---|---|
IECON 18_Proceedings_feedback.pdf
Accesso chiuso
Tipologia:
Pdf editoriale (Version of record)
Licenza:
Tutti i diritti riservati
Dimensione
4.38 MB
Formato
Adobe PDF
|
4.38 MB | Adobe PDF | Richiedi una copia |
I documenti in FLORE sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.