A new general thermodynamic mapping of desiccant systems’ performance is conducted to estimate the potentiality and determine the proper application field of the technology. This targets certain room conditions and given outdoor temperature and humidity prior to the selection of the specific desiccant material and technical details of the system configuration. This allows the choice of the operative state of the system to be independent from the limitations of the specific design and working fluid. An expression of the entropy balance suitable for describing the operability of a desiccant system at steady state is obtained by applying a control volume approach, defining sensible and latent effectiveness parameters, and assuming ideal gas behaviour of the air-vapour mixture. This formulation, together with mass and energy balances, is used to conduct a general screening of the system performance. The theoretical advantage and limitation of desiccant dehumidification air conditioning, maximum efficiency for given conditions constraints, least irreversible configuration for a given operative target, and characteristics of the system for a target efficiency can be obtained from this thermodynamic mapping. Once the thermo-physical properties and the thermodynamic equilibrium relationship of the liquid desiccant mixture or solid coating material are known, this method can be applied to a specific technical case to select the most appropriate working medium and guide the specific system design to achieve the target performance.

Thermodynamic Analysis of Irreversible Desiccant Systems / Rocchetti A., Giannetti N., Yamaguchi S., Kiyoshi S.. - In: ENTROPY. - ISSN 1099-4300. - ELETTRONICO. - 20:(2018), pp. 1-13. [10.3390/e20080595]

Thermodynamic Analysis of Irreversible Desiccant Systems

Rocchetti A.;
2018

Abstract

A new general thermodynamic mapping of desiccant systems’ performance is conducted to estimate the potentiality and determine the proper application field of the technology. This targets certain room conditions and given outdoor temperature and humidity prior to the selection of the specific desiccant material and technical details of the system configuration. This allows the choice of the operative state of the system to be independent from the limitations of the specific design and working fluid. An expression of the entropy balance suitable for describing the operability of a desiccant system at steady state is obtained by applying a control volume approach, defining sensible and latent effectiveness parameters, and assuming ideal gas behaviour of the air-vapour mixture. This formulation, together with mass and energy balances, is used to conduct a general screening of the system performance. The theoretical advantage and limitation of desiccant dehumidification air conditioning, maximum efficiency for given conditions constraints, least irreversible configuration for a given operative target, and characteristics of the system for a target efficiency can be obtained from this thermodynamic mapping. Once the thermo-physical properties and the thermodynamic equilibrium relationship of the liquid desiccant mixture or solid coating material are known, this method can be applied to a specific technical case to select the most appropriate working medium and guide the specific system design to achieve the target performance.
2018
20
1
13
Rocchetti A., Giannetti N., Yamaguchi S., Kiyoshi S.
File in questo prodotto:
File Dimensione Formato  
2018_Entropy.pdf

accesso aperto

Tipologia: Pdf editoriale (Version of record)
Licenza: Open Access
Dimensione 1.9 MB
Formato Adobe PDF
1.9 MB Adobe PDF

I documenti in FLORE sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificatore per citare o creare un link a questa risorsa: https://hdl.handle.net/2158/1173571
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 5
  • ???jsp.display-item.citation.isi??? 4
social impact