A prototype ejector chiller with nominal cooling power of 40 kW, designed according to the “CRMC”crite- rion, has been tested by our research group since 2011. The prototype has undergone several refinements and finally has been upgraded to R1233zd(E), which is non-flammable, has low-GWP and favourable ther- modynamic properties, i.e. “dry-expansion”and moderate pressure at generator. In terms of saturation pressure curve, the new fluid is similar to R245fa, which was previously used in the prototype. Hence, R1233zd(E) has been basically used as a “drop-in”replacement. The ejector chiller was tested at different evaporation temperatures (2.5 to 10 °C), typical of air conditioning applications. Saturation temperatures at generator from 95 to 105 °C have been selected as representative of waste-heat recovery. The experi- mental findings prove that the CRMC ejector has a satisfactory performance with the new working fluid.

A heat-powered ejector chiller working with low-GWP fluid R1233zd(E) (Part 1: Experimental results) / Mahmoudian, Jafar; Rocchetti, Andrea; Mazzelli, Federico; Milazzo, Adriano. - In: INTERNATIONAL JOURNAL OF REFRIGERATION. - ISSN 0140-7007. - ELETTRONICO. - 121:(2021), pp. 1-9. [10.1016/j.ijrefrig.2020.10.015]

A heat-powered ejector chiller working with low-GWP fluid R1233zd(E) (Part 1: Experimental results)

Mahmoudian, Jafar;Rocchetti, Andrea;Mazzelli, Federico;Milazzo, Adriano
2021

Abstract

A prototype ejector chiller with nominal cooling power of 40 kW, designed according to the “CRMC”crite- rion, has been tested by our research group since 2011. The prototype has undergone several refinements and finally has been upgraded to R1233zd(E), which is non-flammable, has low-GWP and favourable ther- modynamic properties, i.e. “dry-expansion”and moderate pressure at generator. In terms of saturation pressure curve, the new fluid is similar to R245fa, which was previously used in the prototype. Hence, R1233zd(E) has been basically used as a “drop-in”replacement. The ejector chiller was tested at different evaporation temperatures (2.5 to 10 °C), typical of air conditioning applications. Saturation temperatures at generator from 95 to 105 °C have been selected as representative of waste-heat recovery. The experi- mental findings prove that the CRMC ejector has a satisfactory performance with the new working fluid.
2021
121
1
9
Goal 7: Affordable and clean energy
Goal 13: Climate action
Mahmoudian, Jafar; Rocchetti, Andrea; Mazzelli, Federico; Milazzo, Adriano
File in questo prodotto:
File Dimensione Formato  
Mahomoudianetal2021a.pdf

Accesso chiuso

Descrizione: pdf articolo
Tipologia: Pdf editoriale (Version of record)
Licenza: Tutti i diritti riservati
Dimensione 2.82 MB
Formato Adobe PDF
2.82 MB Adobe PDF   Richiedi una copia
Mahomoudianetal2021a_firstpage.pdf

accesso aperto

Descrizione: article first page
Tipologia: Pdf editoriale (Version of record)
Licenza: Tutti i diritti riservati
Dimensione 1.32 MB
Formato Adobe PDF
1.32 MB Adobe PDF

I documenti in FLORE sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificatore per citare o creare un link a questa risorsa: https://hdl.handle.net/2158/1217188
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 7
  • ???jsp.display-item.citation.isi??? 7
social impact