CO2-DME (Carbon Dioxide-Dimethyl Ether) mixtures raised our interest in the last year as they promise to increase the COP with respect to pure CO2 while maintaining GWP = 1. The mixture can be non-flammable, as far as the percentage of DME is low. This study presents experimental findings obtained from a chiller system utilizing CO2-DME mixtures as the working fluid. The experimental investigation aims to analyse the performance and behaviour of the chiller under varying operating conditions. Key parameters, such as coefficient of performance, cooling capacity, and thermodynamic behaviour are examined to assess the suitability and efficacy of the CO2-DME mixture in chiller applications. The experimental results shed light on the thermodynamic characteristics and operational considerations of the chiller system, providing valuable insights into the potential of CO2-DME mixtures for environmentally friendly, safe and energy-efficient cooling technologies. The experimental findings indicate a maximum increase in COP of 15 % for a mixture comprising 10 % DME, with a condensation temperature of 35 °C. Furthermore, the cooling capacity is reduced only by 7 % in the worst case.

Experimental results on a chiller using a CO2-DME mixture / Vaccaro, G.; Milazzo, A.; Tobaly, P.; Diaby, A.T.; Talluri, L.. - In: INTERNATIONAL JOURNAL OF REFRIGERATION. - ISSN 0140-7007. - ELETTRONICO. - 168:(2024), pp. 662-672. [10.1016/j.ijrefrig.2024.10.002]

Experimental results on a chiller using a CO2-DME mixture

Vaccaro, G.
;
Milazzo, A.;Talluri, L.
2024

Abstract

CO2-DME (Carbon Dioxide-Dimethyl Ether) mixtures raised our interest in the last year as they promise to increase the COP with respect to pure CO2 while maintaining GWP = 1. The mixture can be non-flammable, as far as the percentage of DME is low. This study presents experimental findings obtained from a chiller system utilizing CO2-DME mixtures as the working fluid. The experimental investigation aims to analyse the performance and behaviour of the chiller under varying operating conditions. Key parameters, such as coefficient of performance, cooling capacity, and thermodynamic behaviour are examined to assess the suitability and efficacy of the CO2-DME mixture in chiller applications. The experimental results shed light on the thermodynamic characteristics and operational considerations of the chiller system, providing valuable insights into the potential of CO2-DME mixtures for environmentally friendly, safe and energy-efficient cooling technologies. The experimental findings indicate a maximum increase in COP of 15 % for a mixture comprising 10 % DME, with a condensation temperature of 35 °C. Furthermore, the cooling capacity is reduced only by 7 % in the worst case.
2024
168
662
672
Goal 7: Affordable and clean energy
Vaccaro, G.; Milazzo, A.; Tobaly, P.; Diaby, A.T.; Talluri, L.
File in questo prodotto:
File Dimensione Formato  
Vaccaro2024.pdf

accesso aperto

Tipologia: Pdf editoriale (Version of record)
Licenza: Open Access
Dimensione 4.39 MB
Formato Adobe PDF
4.39 MB Adobe PDF

I documenti in FLORE sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificatore per citare o creare un link a questa risorsa: https://hdl.handle.net/2158/1410333
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 1
  • ???jsp.display-item.citation.isi??? 1
social impact