Nowadays global warming has increased consciousness of the dangers of energy wastefulness: in the last 50 years the temperature of the Earth's surface rose by approximately 1 °C. The building sector is responsible for a very high percentage of world carbon emissions and with the increasing of the request for comfort, heating, ventilation and air conditioning, buildings energy consumption is rapidly growing. Consequently, it appears fundamental the role played by the improvement of buildings energy performance within global policies of emissions reduction. In this context an increasing attention is given to the energy waste reduction in tertiary sector: bars, offices, restaurants, meetings, shops, school buildings, gyms and in general in the buildings in which the minimization of the energy dissipation is requested. The present study is part of the NANOFANCOIL project (POR-FESR 2014-2020): one of the objectives was the design and implementation of a modulating test plant to assess the performance of innovative cross-flow heat recovery units for air conditioning system. This experimental setup was mainly composed by two climatic chambers that enabled to simulate the environmental conditions of interest. The temperature could vary from -20°C to 0°C and from 10°C to 30°C for the cold and the hot chamber, respectively (i.e. the outdoor and the indoor environment). Moreover, the climatic chamber that simulates the indoor environment could be controlled also in terms of humidity thanks to a steam humidifier that guaranteed 5 kg/h of vapour. Preliminary results about the heat transfer behaviour of a cross-flow heat recovery unit (air-to-air) for controlled mechanical ventilation systems that employs mini-channels in order to increase performance and reduce size and costs are presented here.

Design and implementation of a modulating test plant to assess the performance of innovative cross-flow heat recovery units for air conditioning system: Preliminary results / Bonfiglio C.; Bozzoli F.; Cattani L.; Pagliarini G.; Rainieri S.; Vilar Frana M.; Vocale P.. - In: JOURNAL OF PHYSICS. CONFERENCE SERIES. - ISSN 1742-6588. - 1599:(2020), p. 012026. ( 37th UIT Heat Transfer Conference and Symposium Refrigerants: Heat Transfer and Applications University of Padova, ita 2019) [10.1088/1742-6596/1599/1/012026].

Design and implementation of a modulating test plant to assess the performance of innovative cross-flow heat recovery units for air conditioning system: Preliminary results

Bozzoli F.;
2020

Abstract

Nowadays global warming has increased consciousness of the dangers of energy wastefulness: in the last 50 years the temperature of the Earth's surface rose by approximately 1 °C. The building sector is responsible for a very high percentage of world carbon emissions and with the increasing of the request for comfort, heating, ventilation and air conditioning, buildings energy consumption is rapidly growing. Consequently, it appears fundamental the role played by the improvement of buildings energy performance within global policies of emissions reduction. In this context an increasing attention is given to the energy waste reduction in tertiary sector: bars, offices, restaurants, meetings, shops, school buildings, gyms and in general in the buildings in which the minimization of the energy dissipation is requested. The present study is part of the NANOFANCOIL project (POR-FESR 2014-2020): one of the objectives was the design and implementation of a modulating test plant to assess the performance of innovative cross-flow heat recovery units for air conditioning system. This experimental setup was mainly composed by two climatic chambers that enabled to simulate the environmental conditions of interest. The temperature could vary from -20°C to 0°C and from 10°C to 30°C for the cold and the hot chamber, respectively (i.e. the outdoor and the indoor environment). Moreover, the climatic chamber that simulates the indoor environment could be controlled also in terms of humidity thanks to a steam humidifier that guaranteed 5 kg/h of vapour. Preliminary results about the heat transfer behaviour of a cross-flow heat recovery unit (air-to-air) for controlled mechanical ventilation systems that employs mini-channels in order to increase performance and reduce size and costs are presented here.
2020
Journal of Physics: Conference Series
37th UIT Heat Transfer Conference and Symposium Refrigerants: Heat Transfer and Applications
University of Padova, ita
2019
Bonfiglio C.; Bozzoli F.; Cattani L.; Pagliarini G.; Rainieri S.; Vilar Frana M.; Vocale P.
File in questo prodotto:
File Dimensione Formato  
Bonfiglio_2020_J._Phys.__Conf._Ser._1599_012026 air.pdf

Accesso chiuso

Licenza: Tutti i diritti riservati
Dimensione 696.32 kB
Formato Adobe PDF
696.32 kB Adobe PDF   Richiedi una copia

I documenti in FLORE sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificatore per citare o creare un link a questa risorsa: https://hdl.handle.net/2158/1443430
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 1
  • ???jsp.display-item.citation.isi??? 1
social impact