The aim of this work is to provide a simple and useful tool to study energy performance of different ventilated facades typology. To simulate the studied sample, a steady state energy balance has been applied to a control volume which basic equations have been solved by a finite element code with an iterative procedure. For each step x of the channel height, the different surface and air mass temperatures are calculated. The mass flow rate is evaluated as overall natural draught. Effects due to different cavity widths of the ventilation channel are investigated for winter and summer season with opened and closed ends. Comparisons show that it is possible to obtain a sensible solar cooling effect during summer, when the air cavity width of the chimney is wider than 7 cm. For wider cavities the cooling effect becomes stable. In winter, thermal insulation, provided by the closed ventilated façade is very important.
A simple model to study ventilated facades energy performance / C. BALOCCO. - In: ENERGY AND BUILDINGS. - ISSN 0378-7788. - STAMPA. - 34:(2002), pp. 469-475. [10.1016/S0378-7788(01)00130-X]
A simple model to study ventilated facades energy performance
BALOCCO, CARLA
2002
Abstract
The aim of this work is to provide a simple and useful tool to study energy performance of different ventilated facades typology. To simulate the studied sample, a steady state energy balance has been applied to a control volume which basic equations have been solved by a finite element code with an iterative procedure. For each step x of the channel height, the different surface and air mass temperatures are calculated. The mass flow rate is evaluated as overall natural draught. Effects due to different cavity widths of the ventilation channel are investigated for winter and summer season with opened and closed ends. Comparisons show that it is possible to obtain a sensible solar cooling effect during summer, when the air cavity width of the chimney is wider than 7 cm. For wider cavities the cooling effect becomes stable. In winter, thermal insulation, provided by the closed ventilated façade is very important.File | Dimensione | Formato | |
---|---|---|---|
En&BuildCBalocco_2002.pdf
Accesso chiuso
Tipologia:
Pdf editoriale (Version of record)
Licenza:
Tutti i diritti riservati
Dimensione
244.66 kB
Formato
Adobe PDF
|
244.66 kB | Adobe PDF | Richiedi una copia |
I documenti in FLORE sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.