A 40 kWc jet-pump chiller has been built in Florence at Frigel s.p.a. The plant is intended as a test bench for future jet-pump chillers for applications in the industrial temperature control market and powered by waste heat from CHP systems. The generator and evaporator of the prototype unit are water-heated and the condenser is water cooled. R245fa has been chosen as the working fluid. The prototype’s jet-pump has a movable primary nozzle and 7 static pressure probes on the mixing chamber/diffuser duct. This latter has a profile inspired by the CRMC (Constant Rate of Momentum Change) criterion and is manufactured in carbon fibre and epoxy resin. This paper describes the prototype and presents a preliminary set of experimental test results.
The design and manufacture of a 40 kW jet-pump chiller for air conditioning and industrial application / Ian W. Eames; Adriano Milazzo; Dario Paganini; Michele Livi. - ELETTRONICO. - (2012), pp. 1-6. (Intervento presentato al convegno Heat Powered Cycles 2012 tenutosi a Alkmaar (NL) nel 10-12/9/2012).
The design and manufacture of a 40 kW jet-pump chiller for air conditioning and industrial application
MILAZZO, ADRIANO
;PAGANINI, DARIO;
2012
Abstract
A 40 kWc jet-pump chiller has been built in Florence at Frigel s.p.a. The plant is intended as a test bench for future jet-pump chillers for applications in the industrial temperature control market and powered by waste heat from CHP systems. The generator and evaporator of the prototype unit are water-heated and the condenser is water cooled. R245fa has been chosen as the working fluid. The prototype’s jet-pump has a movable primary nozzle and 7 static pressure probes on the mixing chamber/diffuser duct. This latter has a profile inspired by the CRMC (Constant Rate of Momentum Change) criterion and is manufactured in carbon fibre and epoxy resin. This paper describes the prototype and presents a preliminary set of experimental test results.File | Dimensione | Formato | |
---|---|---|---|
fhpc600.pdf
Accesso chiuso
Tipologia:
Versione finale referata (Postprint, Accepted manuscript)
Licenza:
Tutti i diritti riservati
Dimensione
776.44 kB
Formato
Adobe PDF
|
776.44 kB | Adobe PDF | Richiedi una copia |