A novel technique that relies solely on cost-effective and non-intrusive instrumentation for monitoring the performance of air conditioning installations in buildings was developed and experimentally tested. The proposed method addresses the challenges of field measurements in air-to-air units by using thermocouples and strain gauges placed strategically on the refrigerant pipeline of the outdoor unit to estimate the cycle COP. The tests demonstrated the feasibility of estimating refrigerant temperature and pressure without cutting the refrigerant pipeline. Real-time cycle COP deviations could be limited to 3 % with proper calibration of the strain signal and the use of refrigerant properties. Additionally, compressor speed is identified through the frequency spectrum of the strain signal. Therefore, the refrigerant flow rate can be estimated using a compressor curve method that relies exclusively on simple instrumentation. Widespread adoption of this method could help close the knowledge gap between catalogue and field-operating performance of the numerous air conditioning installations.

Non-intrusive performance monitoring method for air conditioners / Giannetti N.; Yin J.; Miyaoka Y.; Talluri L.; Milazzo A.; Tanaka K.; Kowa W.; Saito K.. - In: INTERNATIONAL JOURNAL OF REFRIGERATION. - ISSN 0140-7007. - ELETTRONICO. - 181:(2026), pp. 74-83. [10.1016/j.ijrefrig.2025.10.003]

Non-intrusive performance monitoring method for air conditioners

Giannetti N.
Conceptualization
;
Talluri L.
Supervision
;
Milazzo A.
Supervision
;
2026

Abstract

A novel technique that relies solely on cost-effective and non-intrusive instrumentation for monitoring the performance of air conditioning installations in buildings was developed and experimentally tested. The proposed method addresses the challenges of field measurements in air-to-air units by using thermocouples and strain gauges placed strategically on the refrigerant pipeline of the outdoor unit to estimate the cycle COP. The tests demonstrated the feasibility of estimating refrigerant temperature and pressure without cutting the refrigerant pipeline. Real-time cycle COP deviations could be limited to 3 % with proper calibration of the strain signal and the use of refrigerant properties. Additionally, compressor speed is identified through the frequency spectrum of the strain signal. Therefore, the refrigerant flow rate can be estimated using a compressor curve method that relies exclusively on simple instrumentation. Widespread adoption of this method could help close the knowledge gap between catalogue and field-operating performance of the numerous air conditioning installations.
2026
181
74
83
Goal 7: Affordable and clean energy
Goal 11: Sustainable cities and communities
Goal 13: Climate action
Giannetti N.; Yin J.; Miyaoka Y.; Talluri L.; Milazzo A.; Tanaka K.; Kowa W.; Saito K.
File in questo prodotto:
File Dimensione Formato  
Giannetti et al IIR 2026.pdf

accesso aperto

Tipologia: Versione finale referata (Postprint, Accepted manuscript)
Licenza: Solo lettura
Dimensione 2.13 MB
Formato Adobe PDF
2.13 MB Adobe PDF

I documenti in FLORE sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificatore per citare o creare un link a questa risorsa: https://hdl.handle.net/2158/1448302
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 0
  • ???jsp.display-item.citation.isi??? 0
social impact